We ordered the wrong one this was never powered up. Specifications—Power Supply Rating 20–40 Vdc for Low Voltage models Power Consumption less than or equal to 15 W nominal Inputs— Load Sensing 90–240 Vac 3ø 45–66 Hz 3ø current transformer input Speed Sensor Input Impedance 100–300 Ω Speed Sensor magnetic pickup 1.0 Vac minimum to 30 Vac maximum Speed Trim 0–100 Ω for 0 to 10% speed change Speed Setting terminals 23–24 jumpered, internally adjustable 100 Ω potentiometer allows external 0–10% speed trim Idle Speed Select external switch, open terminals 19 to 16 Droop external switch, open terminals 14 to 16 Synchronizer ±5 Vdc for speed change with Woodward SPMA synchronizer Load Sharing 0–6 Vdc Outputs— Actuator 7.5 Vdc max for 0 to 214 mA with 35 Ω coil Adjustments— Rated Speed 11 450 Hz Acceleration Ramp (±Idle to Rated) 0–10 s, switch activated, close terminals 19 to 16 Actuator Compensation time constant compatibility 0–500 ms Low Idle Speed 55% rated Load Gain 6 Vdc maximum at 5 A CT current Droop 0 to 10% Speed Control Range switch selectable, 500–1500 Hz, 1000–3000 Hz, 2000–6000 Hz (standard), 4000–12 000 Hz Operating Temperature –40 to +85 °C (–40 to +185 °F) Load Sharing ±5% of rated load with speed setting matched Vibration 4 Gs, 5 to 500 Hz Shock 60 Gs Weight approximately 1.8 kg (4 lb) Finish gloss powder